| Model |
EA2012EMH |
EA3024EMH |
| Input Formation |
L+N+PE |
| AC Input |
220/230/240VAC |
| Input Voltage Range |
90-280VAC±3V(Normal Mode) 170-280VAC±3V (UPS Mode) |
| Frequency |
50/60Hz(Adaptive) |
| Rated Power |
1600W |
3000W |
| Output Voltage |
220/230/240VAC±5% |
| Output Frequency |
50/60Hz±0.1% |
| Output Wave |
Pure Sine Wave |
| Transfer Time(Adjustable) |
10ms for Computer Equipment,20ms for Household Equipment |
| Peak Power |
3200VA |
6000VA |
| Overload Ability |
Battery Mode: 11s@105%~150% Load; 2s@150%~200% Load; 400ms@>200% Load |
| Rated Voltage |
12VDC |
24VDC |
| Constant Charging Voltage |
14.1VDC |
28.2VDC |
| Float Charging Voltage |
13.5VDC |
27VDC |
| PV Charging Method |
MPPT |
| Max PV Input |
2000W |
3000W |
| MPPT Tracking Range |
30~500VDC |
| MAX PV Input Voltage |
500VDC |
| MAX PV Charge Current |
100A |
| MAX AC Charge Current |
60A |
| MAX Charge Current |
100A |
| LCD |
Can display operating mode/load/input/output |
| RS232 |
5PIN/Pitch2.54mm,Baud Rate 2400 |
| Expansion Slot Communication Interface |
Lithium Battery BMS Communication Card,WIFI 2×5PIN/Pitch2.54mm |
| Parallel Interface |
Not Support Parallel |
| Operating Temperature |
-10°C~50°C |
| Storage Temperature |
-15°C~60°C |
| Ork Altitude |
Altitude ≤1000 m; above 1000 m, rated power derates. Max. altitude 4000 m. See the reference. |
| Operating Environment Humidity |
Non Condensing |
| Noise |
≤50dB |